Galleon Tower Series (1.5k/2k/3k/6k)

The Galleon UPS provides high density, true double-conversion on-line power protection. It is ideal for servers, networks applications, as well as for industrial applications.

Features:

  • True double-conversion
  • DSP technology guarantees high performance
  • Output Power Factor 0.8
  • Wide input voltage range (110-300 VAC)
  • Active input power factor correction 0.99
  • 50Hz / 60Hz frequency converter mode
  • Eco mode operation for energy saving (ECO)
  • Programmable power management outlets
  • Emergency power off function (EPO)
  • Generator compatible
  • Charger capacity expansion to 8A for long-run models
  • SNMP + USB + RS – 232 multiple communications
  • 3-stage extendable charging design for optimized battery performance
  • Adjustable battery numbers
  • Maintenance bypass available
  • Optional N+X parallel redundancy

Specifications:

Model Galleon
TW 1.5k
Galleon
TW 2k
Galleon
TW 3k
Galleon
TW 6k
Capacity 1500 VA / 1200W 2000 VA / 1600W 3000 VA / 2400W 6000 VA / 4800 W
Input Voltage Range 110-300 VAC ±5% 110-300 VAC ±3%
Input Frequency 40Hz or 70Hz 46Hz or 70Hz
Output Voltage ± 3% (Batt. Mode) ± 1% (Batt. Mode)
Output Frequency Range 47.5 Hz ~ 52.5 Hz or 57Hz ~ 63 Hz (Synchronized Range)/ 50 Hz ±0.25 Hz or 60 Hz ±0.3 Hz (Batt. Mode) 46 Hz ~ 54 Hz or 50 Hz /56 ~ 64 Hz / 60 Hz
Output Transfer Time (Typical) 4ms (Inverter to Bypass) Zero
Output Waveform (Batt. Mode) Pure Sinewave
Battery Type & Number 12V / 9Ah x 3 12V / 7Ah x 6 12V / 9Ah x 6 12V / 7Ah x 20
Backup Time (One PC load@120W) N/A
Typical Recharge Time (up to 90% capacity) 4 hours 4 hours 4 hours 7 hours
Indicators / AC Mode
Indicators / Battery Mode
Indicators / Fault
Overload Protection
Discharge Protection
Overcharge Protection
Alarm / Battery Mode Sounding every 4 seconds
Alarm / Low Battery Sounding every second (Batt. Mode)
Alarm / Overload Sounding twice per second
Alarm / Battery Replacement Alarm N/A
Alarm / Fault Continuously sounding
Output Receptacles N/A
Physical Dimension (mm) N/A 421 x 190 x 318 421 x 190 x 318 N/A
Physical Net Weight (kg)
Standard Model
14 26 28.6 81
Physical Net Weight (kg)
Long-run Model
6.9 13  13  25
Operating Environment / Humidity 20-90 % RH @ 0- 40°C (non-condensing)
Operating Environment / Noise Level Less than 45dB @ 1 Meter
Management / Optional USB / RS-232 Port Supports Windows® 98/2000/2003/XP/Vista/2008, Windows® 7, Linux, and MAC

 

Comments are closed